A Comparison of Linear Heat Detection Technologies

Linear Heat Detector Comparison Chart
Feature Protectowire Digital Analog Integrating (1) Continuous
Thermocouple (1)
Maximum Zone Length

Up to 5,000 FT. (1,524 m)

1,500 FT. (457.2m)

2,000 FT. (609.6m)

Alarm Point Location

YES

NO

NO

Multiple Alarm Points Within Zone

YES

NO

NO

Underwriters Laboratory (UL) Listed

YES

NO

NO

Factory Mutual (FM) Approved

YES

YES

NO

Alarm Point Setting  Unaffected by Changes in Ambient Temperature

YES

NO

YES

Compatible with Standard Initiating Devices (Manual Stations, Contact Devices and Smoke Detectors)

YES

NO

NO

Pre-Alarm Capability

YES

YES

YES

Approved for use in Hazardous Locations

YES

YES

? *

Easy to Splice / Terminate

YES

NO

? *

Maximum Alarm Temperature

356°F (180°C)

500°F (260°C)

350°F (177°C)

Expected Service Life

Current Installations Greater than 20 Years

? *

? *

Requires On Site Calibration

NO

YES

NO

Size

5/32 in. (4 mm)

0.09 in. (2.28 mm)

1/8 in. (3.175 mm)

Annual Maintenance per NFPA 72, 1999

Minimal

Heat Test - Must alarm within 1 minute

? *

Accuracy dependent on length

NO

YES

NO

Designed and Manufactured by and ISO-9001 Registered Company

YES

? *

? *

Feature

Protectowire Digital

Analog Integrating (1)

Continuous
Thermocouple (1)

(1) - Based on available information at the time of publication 4/13/01
? * - Information unknown or not available